Radiant Heat Flux Test Device For Paving Materials
Heat Flux Meter Measurement Range:
(0-15) Kw / M2
Accuracy Of Heat Flux Meter:
±0.2Kw/m2
Heat Flux Meter Accuracy:
<±3%
Accuracy:
± 0.5 ° C
Black Body Temperature Error:
± 5 ° C
Specimen Holder:
1140 X 320 Mm
Specimen Dimension:
(1050+/-/5) Mm X (230+/-15) Mm
SKYLINE:
Radiant Heat Flux Test Device For Paving Materials
Heat Flux Meter Measurement Range:
(0-15) Kw / M2
Accuracy Of Heat Flux Meter:
±0.2Kw/m2
Heat Flux Meter Accuracy:
<±3%
Accuracy:
± 0.5 ° C
Black Body Temperature Error:
± 5 ° C
Specimen Holder:
1140 X 320 Mm
Specimen Dimension:
(1050+/-/5) Mm X (230+/-15) Mm
Product Description

Radiant Heat Flux Test Device for Paving Materials

 

Application

It is suitable for testing with paving materials that are placed in a small flame and placed horizontally and exposed to a slanted heat radiation field.

Such as: textile carpets, cork boards, wood boards, rubber sheets and plastic floor and floor coating materials. The device may reflect the burning properties of the flooring material including the substrate used, the backing material, the underlying material or other changes in the flooring material may affect the test results, which are used for testing and description under laboratory control conditions, The burning properties of the ground material against the thermal reaction of the fire.

 

Technical Parameters
Heat flux meter measurement range: (0-15) Kw / m2;
Accuracy of heat flux meter: ±0.2Kw/m2;
Heat flux meter accuracy: <±3%;
Thermal radiation high temperature measuring range: 400-600 ° C, accuracy is ± 0.5 ° C;
Black body temperature error: ± 5 ° C;
Smoke exhausting speed: (2.5±0.2) m/s; smoke exhausting capacity: (39-85) m3/min;
Porous refractory radiant panel size: 300mm × 450mm, can withstand high temperatures of about 900 ° C;
Thermocouple: a K-type stainless steel armored thermocouple with a diameter of 3.2 mm;
Heat flux distribution requirements: at 200mm: (9.1 ± 0.4) KW / m2;
At 400mm: (5.0 ± 0.4) KW / m2;
At 600mm: (2.4 ± 0.2) KW / m2;
Combustion gas: propane. (prepared by customer);
Combustion gas flow rate: (0.026 ± 0.002) L / S;
Burning torch: outer diameter ¢ 10mm inner diameter ¢ 6mm, 35 ¢ 0.7mm holes on the burner tube;
Flame height: adjustable from 60 to 120 mm;
Ignition system: high voltage electronic ignition;
Powerful exhaust system: This machine is equipped with a powerful exhaust fan. When the test is completed, the exhaust fan system is activated to exhaust the exhaust gas to the outside.
Burning box size: L1420*W1200*H2300 (mm)
Control box / combustion box material: high quality (t = 1.2mm) 304 non-steel plate, CNC machine tool processing, arc shape is beautiful and generous.
Blowtorch: Made by our company, 304 stainless steel material, fully meet the requirements of GB/T11785 standard.
Other mechanical parts are made of 304 stainless steel or A3 thick plated, anti-corrosion and anti-rust.

Critical Radiant Flux Flammability Testing Equipme...