SKYLINE INSTRUMENTS CO.,LTD info@skylineinstruments.com 86-769-23830463

SKYLINE INSTRUMENTS CO.,LTD Company Profile
products
Home > products > Building Materials Flammability Tester > Building Materials Flammability Tester Touch Screen Steel - Structure Fireproof Coating Sample Test Furnace

Building Materials Flammability Tester Touch Screen Steel - Structure Fireproof Coating Sample Test Furnace

Product Details

Place of Origin: CHINA

Brand Name: SKYLINE

Certification: CE

Model Number: GJL-2

Payment & Shipping Terms

Minimum Order Quantity: 1 unit

Price: negotiated

Packaging Details: plywood case

Delivery Time: 10 work days

Payment Terms: T/T, L/C, Western Union, MoneyGram

Supply Ability: 1 unit/ month

Get Best Price
Product Details
Highlight:

horizontal flammability tester

,

vertical flammability chamber

Standards:
GB 14907-2002 Steel-Structure Fireproof Coating,GB T9978-2008 Fire Resistance Test Method For Building Components, GB T23864-2009 Plugging Material Of Fireproof
Operating Voltage:
AC 380V±10% 50Hz
Air Flow:
0-50 M³/min Measurement Accuracy: ≤ +/-0.5 M³/min
Timing Range:
0-360 Min;Timing Accuracy: < +/-2s
Maximum Of Burning Length Of The Sample:
1600mm
Standards:
GB 14907-2002 Steel-Structure Fireproof Coating,GB T9978-2008 Fire Resistance Test Method For Building Components, GB T23864-2009 Plugging Material Of Fireproof
Operating Voltage:
AC 380V±10% 50Hz
Air Flow:
0-50 M³/min Measurement Accuracy: ≤ +/-0.5 M³/min
Timing Range:
0-360 Min;Timing Accuracy: < +/-2s
Maximum Of Burning Length Of The Sample:
1600mm
Product Description
Steel-Structure Fireproof Coating Sample Test Furnace High Accuracy 3KW
 

Technical indicators

 Operating Voltage  AC 380V +/-10% 50Hz ; Electric power: 3KW
 Stove  Pressure Measurement Range  0-100Pa Measurement Accuracy: ≤ +/-3Pa
 Air Flow  0-50 m³/min Measurement Accuracy: ≤ +/-0.5 m³/min
 Burning Airflow  Propane ,Liquefied gas
 Gas Flow  0-100 L/min;Measurement Accuracy:2.5 level
 Tank Capacity  50 kg*2
 Test Temperature  Program warming:60min room temperature-925℃;120min room temperature-1050℃;180min room temperature-1115℃;240min room temperature-1150℃;300min room temperature-1180℃; 360min room temperature-1210℃;
 Equipment Precision  a.furnace temperature: +/-15℃;b.internal specimen temperature: +/-10℃; c.backfire specimen temperature: +/-4℃
 Temperature Sensor  a.armored platinum rhodium platinum value S thermocouple
accuracy class:II level;b.armored nickel-chromium nickel-silicon value K thermocouple
accuracy class:II level
 Timing Range  0-360 min;Timing Accuracy: < +/-2s
 Maximum of  Burning Length of the Sample  1600mm
 Instrument Dimensions  Test plate bracket 670mm*670mm*1100mm;Control box 800mm*500mm*500mm

 

Features
1.PLC+NA view professional software, touch screen control, easy operation
2. The whole process of testing is fully automated
3. Temperature errors are lower than the national standard

 

Design Standards
GB14907-2002 Steel-Structure Fireproof Coating
GB T9978-2008 Fire Resistance Test Method for Building Components
GB T23864-2009 Plugging Material of Fireproof